How to use NG-Trace with the IEC 60870-5-104 driver?

Valid for IEC-104 library version 2.5.207.

We assume that you have correctly installed NG-Trace and the Fbox library according to this instruction: www.engiby.ch/ngtrace/ngtrdnld.htm.
You have already created your IEC 60870-5-104 application and therefor, you have an S-Fup file with the IEC Driver Fbox.

1 – Open the S-Fup file with the IEC Fbox. Before the IEC Driver Fbox, place an Fbox Trace Buffer from the NG-Trace family. Give him the name 'IEC104'.
On the Fbox enter a free register (one single free register).

2 – In the CPU, create a new file with the type NG-Trace. Important: Uncheck the option 'Linked/Build'. The NG-Trace will open.
            When prompted, select 'Connect to standard buffer'.

3 – Go in the Settings tab and enter the same start register as chosen above. Save the settings.

4 – Build, load and run your program as usual in the PG5 Project Manager. During build, you should get these 2 messages:
                NG-Trace Buffer for IEC104 created.
                NG-Trace Buffer for IEC 60870-5-104 found.
            Only if you get these 2 messages, the trace buffer will work.

5 - Go online with the PG5 Project Manager.

6 - In the View tab of the NG-Trace, press the Connect and the Start buttons.

The named columns appear and the events are recorded. If the options are checked, the PC Date, PC Time and PCD status are added.

In the Frm column you can find the IEC frame types (I-S-U) but also the following:
- Info                     For auxiliary information (e.g. Library version). See Value column
- Error                    For driver errors with error code in ASDU and argument in Value column
- PPP                     For PPP events, with changed status in COT and new status in Value column
- TCP                     For TCP event shown in COT column

Read the Help file for more explanation about the use of NG-Trace.

Back to NG-Trace download page.

 